Reliability Evaluation of 11kv Distribution System in the Presence of Distributed Generation
Article PDF

Keywords

PSO, Electrical Transient Analyzer Program, Distributed Generation, SAIFI, IEEE, ASAI

How to Cite

OKOGBULE, U. S., & EKERIANCE, D. E. (2025). Reliability Evaluation of 11kv Distribution System in the Presence of Distributed Generation. Engineering Research Journal, 5(4), 1-11. https://www.openjournals.ijaar.org/index.php/erj/article/view/1456

Abstract

This paper evaluates the reliability of a typical 11kV distribution system in Nigeria using one year outage frequency and duration data gotten from the utility company.  The reliability performance of the system was assessed by determining key reliability indices, and proposes inclusion of distributed generation (DG) to enhance the indices, since the set standard was not met. Electrical Transient Analyzer Program (ETAP) software was used for the simulation. This was done by carrying out reliability study of the existing 11kV distribution network using embedded analytical equations in ETAP; reliability indices were determined, and improved upon by the penetration of PSO optimized distributed generation (1.63MVA) in bus 9 and reliability study was performed with DG deployment. The results obtained show that at the instant of DG injection into the system, average failure rate and average outage duration at load point 6, reduces by 34.2% and 23.8% respectively, then, it continues so up to load point 14. Similarly, at the penetration of DG, there were significant improvement in the customer’s oriented reliability indices; SAIFI, 0.4747 to 0.2535f/yr, SAIDI, 13.56 to 8.2585hr/yr, CAIDI, 32.577 to 28.581hr.intr and EENS, 56.216 to 43.376MWhr/yr. The availability index ASAI improved from 86.8 % to 99.85% which is close to the 99.9989% IEEE benchmark.

Article PDF
Creative Commons License

This work is licensed under a Creative Commons Attribution-NonCommercial 4.0 International License.

Copyright (c) 2025 Engineering Research journal

453 324